Cold refrigerator matching cold air blower:

The load per cubic metre is calculated according to W0=75W/M3.


If V (cold storage volume) <30m3, door opening times more frequent cold storage, such as fresh meat storehouse, then multiply coefficient a=1.2;


If 30m3≤V<100m3, the number of open doors more frequent cold storage, such as fresh meat storehouse, then multiply coefficient a=1.1;


If V≥100m3, the number of open doors more frequent cold storage, such as fresh meat storehouse, then multiply coefficient a=1.0;


If for a single cold storage, then the coefficient b=1.1 final cold air cooler matching by w=a*b*w0 (W for the cooling fan load);


The matching of cold storage refrigerating machine and cooler is calculated by -10oc evaporation temperature.