Problems and solutions for liquid refrigerant in refrigeration system - 10
Jun 20, 2018

Oil separator 


    The oil separator cannot solve the oil recovery fault caused by the system design, nor can the liquid refrigerant control fault be solved. However, when the system control failure can not be resolved by other means, the oil separator helps to reduce the amount of oil circulating in the system, can help the system through a period of crisis until the system control device back to normal.

    For example: In an ultra-low temperature device or full liquid evaporator, the return oil may be affected by defrosting, in which case the oil separator can help maintain the amount of frozen oil in the compressor during the system defrost period.