    Cooling performance of water-cooled condenser condenser: by ambient wet bulb temperature, the higher the ambient wet bulb temperature, the higher the condensation temperature. 

    Generally, the use of water-cooled condenser, condensation temperature than the ambient wet bulb temperature 5~7℃ about. Condensation temperature limit of general refrigeration system: no higher than 55 ℃, not less than 20 ℃. In general, water-cooled condensers are not recommended in areas where the ambient wet bulb temperature exceeds 42 ℃. 

    So whether you can choose water-cooled condenser, first of all to confirm the ambient wet bulb temperature. When designing water-cooled ice-making machines in general, customers must be required to provide the highest ambient wet bulb temperature of the year. At the same time when the ambient temperature of more than 50 ℃, also can not use water cooling condenser, cooling tower is prone to high temperature drying. The cooling tower must be used in the case of shading protection.